CROUZET CONTROL
Control relay for monitoring of 3-phase networks with neutral (H3USN) and without neutral (H3US). Adjustable switch at the front for adjustment of correct voltage in 3-phase networks. The switch's position is not registered until the operating voltage is switched on. If the switch position is changed during operation, all LEDs (LED indications) begin to flash but the unit will continue to function normally with the voltage that was set at the most recent power connection. Monitors under-voltage between the phases that can be set between -2 % and -20 % of Un (measurement voltage) and over-voltage that can be set between 2 % and 20 % of Un. Each limit (over-/under-voltage) has its own relay output (R1 Over and R2 Under) and there is an adjustable time delay for each relay output (Tt1 and Tt2), adjustable between 0.3-30 s. H3USN also checks for neutral interruption. Green LED (Un) indicates supply voltage OK. Yellow LED (R) indicates active relay output.
Approvals | CE, CSA, RoHS, UL |
---|---|
Breaking capacity | 5A, 250V AC/DC |
IP Class Connection | IP20 |
IP Class Housing | IP30 |
Lower Limit | -2 - -20% |
Output | 2x Relay |
Selection of rated voltage | 220, 380, 400, 415, 440, 480V |
Supply voltage | 3 x 220-480V AC |
Temperature range bearing, from | -40 °C |
Temperature range bearing, to | 70 °C |
---|---|
Temperature range from | -20 °C |
Temperature range to | 50 °C |
Time Delay On Crossing The Threshold | 0,3-30s |
Time Delay Start | 0,5 s |
Upper Limit | 2 - 20% |
Weight | 130 g |
Control relay for monitoring of 3-phase networks with neutral (H3USN) and without neutral (H3US). Adjustable switch at the front for adjustment of correct voltage in 3-phase networks. The switch's position is not registered until the operating voltage is switched on. If the switch position is changed during operation, all LEDs (LED indications) begin to flash but the unit will continue to function normally with the voltage that was set at the most recent power connection. Monitors under-voltage between the phases that can be set between -2 % and -20 % of Un (measurement voltage) and over-voltage that can be set between 2 % and 20 % of Un. Each limit (over-/under-voltage) has its own relay output (R1 Over and R2 Under) and there is an adjustable time delay for each relay output (Tt1 and Tt2), adjustable between 0.3-30 s. H3USN also checks for neutral interruption. Green LED (Un) indicates supply voltage OK. Yellow LED (R) indicates active relay output.
ComatReleco has launched a new series of push-in sockets specifically designed for time and space savings.
Crouzet has honoured the strong Syrelec time relay traditions established in the 1980s, first by Cronos and Cronos 2 series. Now, Crouzet presents the compact and extremely versatile Syr-Line series.
Can you distinguish between a bifurcated contact and a normal contact at a glance?
The need for flexible, modular systems shapes machine and system engineering. Decentralization of the system components has proven to be an important factor for success.
The PIANO PIC series is designed for applications that require reliable DIN rail power supplies, which are focused to deliver the most widely required customer functionalities. Our PIC units offer this simplicity without making compromises on PULS’ renowned qualities; efficiency, service lifetime, reliability and size.
The new WADI product family by Jacob features a completely redesigned gland rubber, which allows extensive sealing and tightening area.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Articles | Selection of rated voltage | Supply voltage | ||
---|---|---|---|---|
H3US VOLTAGE CONTROL RELAY
Art:
84873220
Copied
|
220, 380, 400, 415, 440, 480V
|
3 x 220-480V AC
|
| |
H3USN VOLTAGE CONTROL RELAY
Art:
84873221
Copied
|
120, 127, 220, 230, 240, 260, 277V
|
3 x 120-277V AC
|
|
Select a variant in the list