• Over 25,000 products in stock
  • clock Stock items ordered before 15:00, will be dispatched on the same day
  • Read more about us
CROUZET CONTROL
CROUZET CONTROL

3 phase, phase control HWUA

  • Triggers alarm upon incorrect phase sequence, phase interruption, asymmetry and over-/under-voltage
  • Adjustable line voltage
  • Measures returned voltage to 70 %
  • 35 mm cabinet with DIN rail

Product description

Control relay for phase monitoring with regeneration of voltage and asymmetry. Adjustable switch at the front for adjustment of correct voltage in 3-phase networks. Voltage switch's position is not registered until the operating voltage is switched on. If the switch position is changed during operation, all LEDs (LED indications) begin to flash but the unit will continue to function normally with the voltage that was set at the most recent power connection. The LEDs return to normal function when the correct voltage is restored. The relay monitors the correct phase sequence between the three phases or if any phase is lacking (measured U<0.7xUn), 70 % of the returned voltage. The asymmetry setting is made at the front between 5 and 15 % (the rated voltage between the phases Un x degree of asymmetry, %). Deviations in over-/under-voltage are adjustable between -2 and -20 % of the line voltage (window relay function). In the event of incorrect phase sequence or phase interruption, the relay immediately produces an alarm (drops out), and in the event of an asymmetry or voltage fault, the relay drops out after the set time Tt. If the power is switched on with a measured fault, the relay remains deactivated. Fault indication is accomplished with LEDs, which also differentiates between the various fault causes. If a fault remains after the time delay, a non-flashing LED indicates an asymmetry fault and a flashing LED indicates over-/under-voltage. The LED indication that shows this is labelled with Def. on the front of the relay. Green LED (Un) indicates supply voltage OK. Yellow LED (R) indicates active relay output.

 

Articles

Variant

Crouzet 3-phase monitoring relay

84873026
Phase Monitor Relay HWUA 3 x 220-480V ac

Specifications

Approvals CSA, GL, RoHS, UL
Breaking capacity 5A, 250V AC/DC
Function Phase Sequence, Phase Failure, Asymmetry, Under/Overvoltage
IP class connection IP20
IP class housing IP30
Mounting 35 mm DIN-Rail
Output Relay
Selection of rated voltage 220, 380, 400, 415, 440, 480 V
Storage temperature max 70 °C
Storage temperature min -40 °C
Supply voltage 3 x 220-480V AC
Temperature operational max 50 °C
Temperature operational min -20 °C
Time delay alarm 0,2 s
Time delay startup 0,5 s
Time delay when exceeding the limit value 0,1-10s
Weight 130 g

Measurements and connections

Technical illustrations

  • F1: Fast-blow fuse 100 mA (recommendation)

    F1: Fast-blow fuse 100 mA (recommendation)

  • Phase interruption, phase sequence and asymmetry<br />1: L1<br />2: L2<br />3: L3<br />4: Limit value for asymmetry<br />5: Hysteresis<br />6: Relay<br />7: Delay upon exceeding limit value Tt

    Phase interruption, phase sequence and asymmetry
    1: L1
    2: L2
    3: L3
    4: Limit value for asymmetry
    5: Hysteresis
    6: Relay
    7: Delay upon exceeding limit value Tt

  • Over and under voltage<br />1: Limit value, over-voltage<br />2: Hysteresis<br />3: Limit value, under-voltage<br />4: L1, L2, L3<br />5: Relay<br />6: Delay upon exceeding limit value Tt<br />

    Over and under voltage
    1: Limit value, over-voltage
    2: Hysteresis
    3: Limit value, under-voltage
    4: L1, L2, L3
    5: Relay
    6: Delay upon exceeding limit value Tt

Contact us

Please contact us for more information.

Send e-mail