CONTA-CLIP
The FDLIS series is a compact terminal designed for the distribution of power.
The range consists of six different blocks that can be used in single or 3 phase installation of up to 32A
Solid wires or stranded cables with ferrules can be directly inserted into the terminals without the need of any tools.
These blocks include a version that connects directly to the din rail for the Earth connection.
Where there is a need to disconnect the Neutral circuit, without the removal of the cables, there is a neutral disconnect terminal that is designed to accommodate a 10 x 3 mm neutral busbar. There is no need for an additional fixing plate because the NT terminal snaps the neutral busbar securely into place.
Articles | Additional information | Connections | KEMA KEUR test standard | Pack Size | Special connections | Weight | Width |
---|---|---|---|---|---|---|---|
![]()
3240.2
FDLIS 2,5-4 NT/L/PE
|
4 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 50 | Busbar 10 x 3mm | 21 g | 5,1 mm | |
![]()
3241.2
FDLIS 2,5-4 N/L/PE
|
5 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 50 | 21 g | 5,1 mm | ||
![]()
3242.2
FDLIS 2,5-4 L/L/PE
|
5 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 50 | 21 g | 5,1 mm | ||
![]()
3243.2
FDLIS 2,5-4 N/L
|
4 | EN 60947-7-1:2009 | 50 | 15,4 g | 5,1 mm | ||
![]()
3244.2
FDLIS 2,5-4 L/L
|
4 | EN 60947-7-1:2009 | 50 | 15,4 g | 5,1 mm | ||
![]()
3245.2
FDLIS 2,5-4 N
|
2 | EN 60947-7-1:2009 | 50 | 11 g | 5,1 mm | ||
![]()
3246.2
FDLIS 2,5-4 L
|
2 | EN 60947-7-1:2009 | 50 | 10 g | 5,1 mm | ||
![]()
3247.2
FDLIS B 2,5-4 3NT/3L/3PE
|
block for AC application | 12 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 16 | Busbar 10 x 3mm | 63 g | 15,3 mm |
![]()
3248.2
FDLIS B 2,5-4 NT/3L/PE
|
block for 3-phase application | 7 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 25 | Busbar 10 x 3mm | 35,78 g | 10,2 mm |
![]()
3249.2
FDLIS B 2,5-4 3L/3N/3PE
|
block for AC application | 15 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 16 | 62 g | 15,3 mm | |
![]()
3250.2
FDLIS B 2,5-4 3L/N/PE
|
block for 3-phase application | 9 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 25 | 37 g | 10,2 mm | |
![]()
3251.2
FDLIS B 2,5-4 6L
|
12 | EN 60947-7-1:2009 | 16 | 47,2 g | 15,3 mm | ||
![]()
3252.2
FDLIS B 2,5-4 6L/3PE
|
15 | EN 60947-7-1:2009, EN 60947-7-2:2009 | 16 | 62 g | 15,3 mm |
Approvals | CSA, CSA US, KEMA KUR, EAC |
---|---|
Color | Beige |
Connections | 4 |
Contamination degree | 3 |
Country of origin | BG |
Cross connect channels | 2 |
Cross section single wire from | 0,2 mm² |
Cross section single wire to | 4 mm² |
Cross section stranded wire from | 0,2 mm² |
Cross section stranded wire to | 4 mm² |
Cross section stranded with ferrule from | 0,2 mm² |
Cross section stranded with ferrule to | 2,5 mm² |
Cross-Section | 4 mm² |
CSA test standard | C22.2 No 158 |
CSAus test standard | UL 1059 |
EAC test standard | TR ZU 004/2011 |
Flamklass | UL94-V0 |
Height TS 35/7.5 | 49 mm |
Insulation Material | Polyamide 6.6 |
KEMA KEUR test standard | EN 60947-7-1:2009, EN 60947-7-2:2009 |
Length | 100 mm |
Load Current Max | 32 A |
Mounting | TS 35/7,5 |
Operating temperature from | -40 °C |
Operating temperature to | 120 °C |
Overvoltage category | III |
Pack Size | 50 |
Plug gauge acc. EN 60 947-1 | A3 |
Rated Current CSA | 25 A |
Rated current CSAus | 25 A |
Rated Current IEC | 32 A |
Rated impulse voltage | 6 kV |
Rated wire cross section from (AWG) | 26 |
Rated wire cross section to (AWG) | 10 |
Rated voltage CSAus | 300 V |
Rated Voltage IEC | 400 V |
Special connections | Busbar 10 x 3mm |
Stripping Length | 12 mm |
Tariff code | 85369010 |
Weight | 21 g |
Width | 5,1 mm |
Voltage CSA | 300 V |